How much backup power do you actually need?

Pick what you want to keep running in an outage. Edit any wattage to match the nameplate on your own appliance; that beats any chart. Everything runs in your browser. Nothing you type is sent anywhere.

Safety first.
  • Never backfeed a generator by plugging it into a wall outlet. It can electrocute utility line workers and neighbors and bypasses your home's protection (CPSC).
  • Connecting any generator or battery to house wiring requires a transfer switch or listed interlock installed by a licensed electrician, with permits where your city or county requires them.
  • Carbon monoxide kills. Run portable generators outside only, at least 20 feet from the house, exhaust pointed away, never in a garage, basement, shed or porch. Install battery-backed CO alarms (CPSC).
  • Planning estimates only. Results are planning estimates, not engineering advice, electrical design, or a substitute for a load calculation by a licensed electrician (for example, a National Electrical Code load calculation). Have a licensed electrician confirm sizing, wiring and any transfer switch before you buy or install. Follow your equipment manuals and local code. Full safety notes & disclaimer.

1. What do you want to power?

Set Qty to 0 to skip an item. "Extra starting watts" is the brief surge a motor needs on top of its running watts. "% of time on" is how much of the outage the item actually draws power (fridges and pumps cycle). Those percentages are editable guesses.

ApplianceQtyRunning WExtra starting W% of time on240 V?

2. Your outage and backup type

Natural gas: standby generators make less power on natural gas than on propane (LP), and how much less varies by model. 87.5% is a conservative default; check your model's spec sheet for its NG rating and enter it here.

Battery assumptions (edit if you know your system)

3. Results

Planning estimates only. Results are planning estimates, not engineering advice, electrical design, or a substitute for a load calculation by a licensed electrician (for example, a National Electrical Code load calculation). Confirm sizing, wiring and any transfer switch with a licensed electrician before you buy or install anything.

Assumptions & sources

  • Default appliance watts come from Generac's RS-series portable generator wattage chart (running watts and additional starting watts; brochure PDF). Lights, router, chargers, CPAP, chest freezer and space heater come from GenSize's planning chart (converted to "extra starting"). These are deliberately conservative planning numbers; your appliance's nameplate or a plug-in meter is more accurate. Modern refrigerators (for example, Energy Star models) often have much lower starting surges than the 2,200 W chart default, so if yours is newer, check the nameplate or measure it.
  • Peak surge = total running watts + the single largest extra starting surge, because motors usually don't start at the same instant. That's the method in the Generac and Champion manuals. Tick the box above to add every surge instead.
  • Energy (kWh) = running watts × % of time on × hours ÷ 1,000, the standard DOE formula (Virginia Cooperative Extension / DOE). The refrigerator's 33% comes from that same source ("divide the time plugged in by three"). Every other % is a labeled guess you should edit.
  • Altitude derate: engine generators lose about 3.5% output per 1,000 ft (Champion 201281 manual).
  • Heat: engines also lose some output in extreme heat. This calculator doesn't model heat derating, so check your generator manual's temperature derating if you'll run it in very hot weather.
  • Fuel derate: propane is 90% of the gasoline rating (Champion 201281: 6,750 W on propane vs 7,500 W on gasoline, spec). Natural gas defaults to 87.5% of the LP rating, and you can edit it. How much a standby unit loses on natural gas varies by model: on Generac's current air-cooled Guardian spec sheets, NG output ranges from the same as LP (14 kW model) to 12.5% lower (24 kW model: 21,000 W on NG vs 24,000 W on LP), so 87.5% matches the biggest drop in that lineup (10–18 kW spec sheet, 20–24 kW spec sheet). Check your own model's spec sheet.
  • Headroom (default 20%) keeps a generator or inverter from running flat out. It's a common design margin, not a code requirement.
  • Battery: inverter efficiency 90% and depth of discharge 90% are assumptions. For reference, Tesla lists 89% solar-to-battery-to-home round-trip efficiency for Powerwall 3 (datasheet). Many spec sheets already list usable kWh, so compare against the "usable" figure when they do. Power factor 0.9 is an assumption used only to convert inverter kW to kVA.
  • Motor starting on a battery inverter depends on its surge rating and locked-rotor-amp (LRA) capability, not just kW. Check the spec or use a soft starter.

Results are brand-neutral planning estimates, not engineering advice and not a guarantee for your home. They are not a substitute for a licensed electrician's load calculation. If we ever show product links next to results, each one is labeled "(paid link)". Learn the method in How to size a home generator and Running vs. starting watts.